PRODUCT DESCRIPTION
Main Features
The MCC Panels are installed in a sewage treatment plant.
There have plant C&D each with 8xAerators,2X mixers and 2X stirers.C&D share the same panel .
The dimension of the panel are L8000XH2000xW600.
MCC Panel Layout
RAS WAS Panel circuit INCOMER

Main MCC Panel Layout

Technical Data
The Doors should be mounted with
Running/trip lights
Emergency stop button
Start/stop buttons
Local/remote selector switch
Ammeters
Voltmeter
Running hour meters
Panel fans
Below are the circuits
16x55kW motors with VSDs.
4X 7.5kW motors with VSDs.
4x5kW motors with VSDs.
incomer with a 2000A circuit breaker and a 2400 A isolator.
Panel with two circuit breakers for C and D ( Splitting the two sections of the plants).
RAS/WAS Isolator.
Distribution board.
All the circuits have the same control philosophy. we just want to start and stop the motors both from remote and local . we have also attached the control of the philosophy 3 circuits.
RAS WAS Panel Diagram
RAS WAS Panel circuit


MCC Panel Diagram
Main MCC Panel circuit