Products

ZJR7-E Series External Bypass Contactor Soft Starter

Main Features 1. With two models of external bypass and internal bypass, it is convenient for customers to choose. 2. Main terminal connecting line is fixed […]

PRODUCT DESCRIPTION

Main Features

1. With two models of external bypass and internal bypass, it is convenient for customers to choose.

2. Main terminal connecting line is fixed directly by screws, which is safe and reliable.

3.The control line alone power supply is more stable, can make the main power supply range covers 220-480V without changing the machine.

4.LCD display, standard Chinese and English options, more convenient to use, can also be customized according to customer requirements of other language types.

5.Three groups  motor parameters can be switched, more convenient to use.

6.With PTC temperature sensor interface, motor protection is more comprehensive.

7.Equipped with RS485 communication interface as standard, it is more convenient for group network control.

8.10 sets fault records, Easier to find problem .

Model Description

Specification

ZJR7-E Series Bypass Contactor Soft Starter

 

Soft starter Model Rated Power (kW) Rated Current (A) Outline Size (mm) Install Size (mm)
H H1 W D H2 W1 W2 Φd
ZJR7-E11T3-S2 5.5kW 11A 290 155 170 272 138 5.5
ZJR7-E15T3-S2 7.5kW 15A 290 155 170 272 138 5.5
ZJR7-E22T3-S2 11kW 22A 290 155 170 272 138 5.5
ZJR7-E30T3-S2 15kW 30A 290 155 170 272 138 5.5
ZJR7-E37T3-S2 18.5kW 37A 290 155 170 272 138 5.5
ZJR7-E44T3-S2 22kW 44A 290 155 170 272 138 5.5
ZJR7-E60T3-S2 30kW 60A 290 155 170 272 138 5.5
ZJR7-E74T3-S2 37kW 74A 290 155 170 272 138 5.5
ZJR7-E90T3-S2 45kW 90A 290 155 170 272 138 5.5
ZJR7-E110T3-S2 55kW 110A 290 155 170 272 138 5.5

 

 

 

Soft starter Model Rated Power (KW) Rated Current (A) Outline Size (mm) Install Size (mm)
H H1 W D H2 W1 W2 Φd
ZJR7-E150T3-S2 75kW 150A 380 360 220 230 340 180 7
ZJR7-E180T3-S2 90kW 180A 380 360 220 230 340 180 7
ZJR7-E220T3-S2 110kW 220A 380 360 220 230 340 180 7
ZJR7-E264T3-S2 132kW 264A 490 447 270 230 422 230 7
ZJR7-E320T3-S2 160kW 320A 490 447 270 230 422 230 7
ZJR7-E370T3-S2 185kW 370A 490 447 270 230 422 230 7
ZJR7-E400T3-S2 200kW 400A 490 447 270 230 422 230 7
ZJR7-E440T3-S2 220kW 440A 490 447 270 230 422 230 7
ZJR7-E500T3-S2 250kW 500A 560 497 310 230 472 270 100 7
ZJR7-E560T3-S2 280kW 560A 560 497 310 230 472 270 100 7
ZJR7-E630T3-S2 315kW 630A 560 497 310 230 472 270 100 7
ZJR7-E710T3-S2 355kW 710A 590 527 350 230 502 300 110 9
ZJR7-E800T3-S2 400kW 800A 590 527 350 230 502 300 110 9
ZJR7-E900T3-S2 450kW 900A 590 527 350 230 502 300 110 9
ZJR7-E1000T3-S2 500kW 1000A 660 577 420 230 552 370 135 9
ZJR7-E1120T3-S2 560kW 1120A 660 577 420 230 552 370 135 9
ZJR7-E1260T3-S2 630kW 1260A 660 577 420 230 552 370 135 9

Technical Indications

Item Item Description
Rated working voltage Three Phase 220-480VAC±10%/50(60)Hz
Rated  limit short-circuit current 20kA (400A and Below) 30kA (400A and above)
Coordination type Type I
Use categories AC-53b
Rated control supply voltage 180-260VAC
Rated insulation voltage 660V
Applicable motors Squirrel-cage three-phase asynchronous motors
Number of starts It’s recommended that No more than 5 times per hour, the number of starts can be set in the parameters
Control mode (1) Operation panel control; (2) External terminal control; (3) Communication control
Start Mode ⑴Voltage ramp starting;

⑵Torque Start;

⑶Kick start+Voltage ramp Start

⑷Kick start +torque start

Stop Mode ⑴Soft Stop; ⑵ Free Stop
Protection Function ⑴Instantaneous stop terminal open circuit fault;

⑵Soft starter overheating; ⑶Motor overheating;

⑷Input Phase loss; (5)Output phase loss;

⑹Three phase unbalance; ⑺Underload protection;

⑻Overload protection; ⑼The power supply voltage is too low;

⑽The power supply voltage is too high;

⑾Error setting parameters;

⑿The load is shorted circuit ;

⒀frequency error;   ⒁External faults;

⒂ The starting time is too long;

⒃ Too many starting times and etc.

Ambient Place to be used Indoor; no corrosive gases, no conductive dust; well ventilated.
Altitude The altitude does not exceed 1000m, if it exceeds 1000m and is less than 3000m, the current is reduced by 1% for each additional 100m.
Ambient temperature Ambient temperature should be between -10℃~+40℃, +40℃~+50℃ should be derated, the current is derated by 2% for every 1℃ rise in temperature.
Ambient humidity The relative humidity is no more  than 90%, without dew condensation .
Vibration Vibration  force should be below 0.5G
Structure Protection Class IP20
Cooling Mode Natural air cooling

Rated Drawings

Standard Wiring Diagram

 

Main Circuit Connection Diagram for built-in bypass Contactor  Type

 

Application Settings

As load conditions change,parameters often need to be adjusted.The following table is for reference only.
Application Starting boost time (s) Stop depressurization time (s) Starting voltage (%) Voltage starting

(current limit value)

Centrifugal Pump 16 20 40 4
Ball Mill 20 6 60 4
Fan 26 4 30 4
Piston Compressor 16 4 40 3
Light Load Motor 16 2 30 3
Lifting  Machinery 6 10 60 3.5
Mixer 16 2 50 4
Crusher 16 10 50 4
Screw

Compressor

16 2 40 3
Spiral Conveyor Belt 20 10 40 4
Belt Conveyor Belt 20 10 40 3
Heat Pump 16 20 40 3